The BlueLinQ Pro is a 1 to 6 pump monitor and controller, designed mainly to be used in municipal wastewater pumping stations. The software included in the BlueLinQ Pro is a further development of the EC 531 and PC 441 controllers. The controller consists of a 7” touch screen display, which can be connected to
a range of modules for monitoring and controlling any pump pit configuration. The back-plane DIN rail power and communication connections and slim-line design of the modules allows for simplified installation and space saving in any electrical cabinet. Monitoring of pump/pit data, viewing of alarms, manual control of pumps and changing of settings etc. can be made locally via the 7” touch screen or via the configuration software AquaProg on a PC, connected directly to the local service port or remotely via modem. Settings are password protected in two levels to avoid unauthorized or accidental changes.

Key control parameters

  • Advanced monitoring of 1-6 pumps
  • Advanced control of 1-6 pumps
  • Communication via modem, RS485, RS232, USB and Ethernet
  • Logging of analogue signals, digital signals and alarms
  • Mixer and drain pump control
  • Advanced pump capacity, inflow and outflow calculation with alarm handling
  • Overflow measurement
  • Best Efficiency Point (BEP) with parallel running pump support
  • Modbus support for external VFD, energy meter etc.
  • Panel mounted

Functions

  • Variable start / stop levels per day and night in a week
  • Alternative stop level
  • Best Efficiency Point
  • Start / Stop based on speed of level change
  • Ratio starts of pumps
  • Random start levels
  • Smart VFD control
  • Auto reverse of pump
  • Max. runtime check
  • Cyclic motion timer
  • Remote blocking of pump via communication
  • Support for controlled pump valves

Sump monitoring function

  • Max. number of pumps running
  • Mixer control logic
  • Drain pump monitoring
  • Level signal check against high/low level sensor and level deviation over time
  • Timer based back-up run of pump via high level float
  • Sump level indication calculated from sump bottom or sea level
  • Support for controlled mains valve

Communication interface

  • 1 RS232 port connects to modem, radio or other serial communication carrier.
  • 1 USB service port
  • 1 Com port for Modbus on TCP, RJ-45 Ethernet
  • 2 ModBus on RS485 (Galvanically Isolated)
  • Register & IO cross reference table

Other functions

  • Micro SD card interface

Modules available for the BlueLinQ Pro

  • BlueLinQ DI-12 module (CA 811)
    Digital Input module for connection of up to 12 Digital Inputs.
    Digital Inputs are divided into 6 groups of 2 galvanically isolated inputs.
  • BlueLinQ DO-8 module (CA 821)
    Digital Output module for the connection of up to 8 Digital
    Outputs. The digital outputs are externally powered in 2 groups of 4 outputs, with each output having a max. load of 1 A (4 A total for all outputs).
  • BlueLinQ AI-6 module (CA 831)
    Analog Input module for connection of up to 6 Analog inputs (4 –20 mA) with a resolution of 0.01 mA.
  • BlueLinQ AO-6 module (CA 841)
    Analog Output module for connection of up to 6 Analog Outputs (4 – 20 mA) with a resolution of 0.01 mA.
  • BlueLinQ LI-6 module (CA 861)
    Leakage module for connection of up to 6 Leakage signals all of which are galvanically isolated from the connecting field bus.
  • BlueLinQ TI-6 module (CA 832)
    Temperature module for connection of up to 6 Temperature signals all of which are galvanically isolated from the connecting field bus.

Technical specifications

Screen Type 7” Touch Screen, 480 * 800 Pixel Resolution
Ambient operating temperature -20 to +50ºC
Ambient storage temperature -30 to +80 °C
Degree of protection Front panel IP65 / Back panel IP20
Housing material Frame: PC UL 94 V0 Rear Hood: Galvanised sheet steel
Mounting Panel Mounted. Cut-out of 208 x 128 mm
Humidity 0-95% RH non condensing
Dimensions (HxWxD)

146 x 226 x 52.5 mm

Power supply 10-30 VDC
Power consumption < 6.0 W
Power consumption max. load < 112 W (30 modules attached)
Installation category  CAT I
Digital outputs  4 Outputs, Positive logic, Sourcing from power Vdo (Pin8), 1.7 A/output, Total Load 4 A
Digital inputs 4 inputs, 1.8 kΩ input resistance, 0-30 V input voltage, 4 V ≈ trig level, 1 kHz max. pulse rate
Field Bus (to CA 811/CA 821... etc. 1 CAN FD Port. Max. current load 6 A
Max. Modules supported on Field Bus 30
Communication ports 1 USB 2.0 service port, 1 RS232 port for telemetry interface (modem), 2 Modbus on RS485 (galvanically isolated), 1 ethernet port for Modbus TCP
Analogue signals 31 days for 32 channels @ 1 min interval
Digital signals and alarms 4096 events
Crash Log 4 logs, 138 parameters, 6 min pre- and 2 min post-crash log initiation, 1 sec resolution
Memory 1 micro SD interface for uploading/downloading updates or data
Max. Altitude 2000 m

 

 