| Ambient operating temperature: |
-20 to +50ºC |
| Ambient storage temperature: |
-30 to +80ºC |
| Cabinet and mounting: |
DIN rail, IP65Mounting holes: see figure |
| Dimensions: |
HxWxD: 370x250x123 mm |
| Weight: |
<5kg, with battery |
| Humidity: |
0-95% RH non-condensing |
| Power supply: |
230/400 VAC,maximum 16A fused |
| Power consumption: |
< 16VA |
| Contactor, max load: |
ABB B7-30-10, 5.5 kW, 12A,coil 24 VAC |
| Fuses (only CP 212): |
3x10A 3-poletype D circuit breakers |
| Fuse for external air pump: |
500mA slow blow |
| Max load on alarm relays: |
250VAC, 4A,100VA resistive load |
| Max current from 12 VDC out: |
50mA |
| Input voltage at Digital In and Block Pump: |
5-24 VDC |
| Resistance at Digital In and Block Pump: |
5 kohm |
| Analogue sensor: |
4-20 mA |
| Analogue input resistance: |
110 ohm |
| Temperature sensor: |
PTC, limit: 3 kohm |
| Leakage sensor: |
Limit: 50 kohm |
| Maximum length of I/O cables: |
30 meters |
| Charge for lead-acid battery: |
Max 80mA, 13.7 VDC |