Sulzer turbocompressor HST 20
Single-stage centrifugal compressor for absolutely oil-free supply of air. The turbocompressor featuring variable speed control for continuously variable power optimization according to the changes in inlet conditions and differential pressure.
Construction
- Frequency converter
- Totally oil-free magnetic bearings
- Blow-off valve with silencer
- Local control
- All safety control required for monitoring
- Sound isolation enclosure
- All mounted on a common base plate
- Integrated high speed electric motor
- Accessories for inlet/outlet (as options)
High speed electric motor
Air cooled variable speed high frequency electric motor. The impeller and the motor cooling fan are mounted directly to the motor shaft. Vertically mounted motor with magnetic bearings and variable rotation speed.
Frequency converter
In-built frequency converter for variable motor speed control and optimal efficiency at all operation points. Start-up with soft start function. Includes RFI-filter that attenuates the radio frequency interference.
Impeller
Impeller shaped from a solid piece of high-strength aluminium alloy on a numerical machining center in CAM technology. Impeller design with 3 dimensional shaped blades, individually optimized to the design range of the compressor.
Magnetic bearings
Two radial bearings with 8 pole magnets each and two axial magnetic bearing with 2 pole magnets each and continuous rotor position measurement controlled by active magnetic bearing controller. Including RFI-filter.
Features:
- No mechanical contact between surfaces
- No mechanical friction
- No wearing
- No oil lubrication
- Vibration free operation
- Continuous rotor balance monitoring and unbalance compensation
Directives
- Machinery Directive (MD), 2006/42/EC, 2009/127/EC.
- Low Voltage Directive (LVD), 2006/95/EC.
- Electromagnetic Compatibility (EMCD), 2004/108/EC.
- Available as CE or UL certified.
The product is designed and manufactured to be connected to industrial network in accordance with EN 61800-3 standard. (EMC product standard for adjustable speed electrical power drive system).
Test run
Performance test and acceptance according to ISO 5389 will be performed on Sulzer test stand and attested. The design values of the performance are guaranteed within a manufacturing tolerance of ± 2%. The measurement uncertainty is evaluated according to ISO 5389.
Cooling air quality
Permitted chemical
vapours according
to IEC 60721-3-3 class 3C3
|
Ave. / Max
[mg/m³]
|
Sulphur dioxide (SO2) |
5,0 / 10 |
Hydrogen sulphide (H2S) |
3,0 / 10 |
Chlorine (Cl) |
0,3 / 1,0 |
Hydrogen chlorine (HCl) |
1,0 / 5,0 |
Hydrogen fluoride (HF) |
0,1 / 2,0 |
Ammonia (NH3) |
10 / 35 |
Ozone (O3) |
0,1 / 0,3 |
Nitrogen oxides (NOx) |
3,0 / 9,0 |
Compressor control
Connections
Analog and Digital I/O as standard
Ethernet
Profibus, Modbus or DeviceNet (as an option)
Local control and monitoring
Color touch screen
Widely customizable monitoring content to suitindividual requirements
Visualized efficiency monitoring for optimal energy usage
Extensive diagnostics, trends and log files
Remote control and monitoring
Available via internet, local network or modem (as an option)
Compressor data
HST 20
|
-4500-1-125
|
-4500-1-150
|
-6000-1-125
|
-6000-1-150
|
-6000-1-190
|
Air flow range [Nm3/h]
|
2000-5500
|
2000-5800
|
2000-6500
|
2000-6750
|
2000-7000
|
Pressure rise [kPa]
|
30-90
|
30-90
|
30-90
|
30-90
|
30-90
|
Max noise level [dB]
|
70
|
70
|
70
|
70
|
70
|
Input power [kW]
|
125
|
150
|
125
|
150
|
190
|
Max. current (400V) [A]
|
198
|
238
|
198
|
238
|
301
|
Max. current (500V) [A]
|
159
|
190
|
159
|
190
|
241
|
Max. current (690V) [A]
|
115
|
138
|
115
|
138
|
175
|
Power supply [V]
|
380-690
|
380-690
|
380-690
|
380-690
|
380-690
|
Input power frequency [Hz]
|
50/60
|
50/60
|
50/60
|
50/60
|
50/60
|
Protection class
|
IP 33D
|
IP 33D
|
IP 33D
|
IP 33D
|
IP 33D
|
Thermal protection
|
Pt100
|
Pt100
|
Pt100
|
Pt100
|
Pt100
|